5.7.4 SELECTOR SWITCH
PATH: SETTINGS
CONTROL ELEMENTS
SELECTOR SWITCH
SELECTOR SWITCH 1(2)
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows set-
ting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set-
ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out
of range.
•
SELECTOR 1 FULL RANGE
: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-
bit control word for programming the selector to a desired position, the change would take place only if the control word
is within the range of 1 to the
SELECTOR FULL RANGE
. If the control word is outside the range, an alarm is established
by setting the
SELECTOR ALARM
FlexLogic operand for 3 seconds.
SELECTOR SWITCH 1
SELECTOR 1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
SELECTOR 1 FULL
RANGE: 7
Range: 1 to 7 in steps of 1
MESSAGE
SELECTOR 1 TIME-OUT:
5.0 s
Range: 3.0 to 60.0 s in steps of 0.1
MESSAGE
SELECTOR 1 STEP-UP:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 STEP-UP
MODE: Time-out
Range: Time-out, Acknowledge
MESSAGE
SELECTOR 1 ACK:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT A0:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT A1:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT A2:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT
MODE: Time-out
Range: Time-out, Acknowledge
MESSAGE
SELECTOR 1 3BIT ACK:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 POWER-UP
MODE: Restore
Range: Restore, Synchronize, Sync/Restore
MESSAGE
SELECTOR 1 TARGETS:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
SELECTOR 1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...