5-230
M60 Motor Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
d) RESTART DELAY
PATH: SETTINGS
CONTROL ELEMENTS
START SUPERVISION
RESTART DELAY
The
RESTART DELAY MIN TIME
setting specifies the lockout time to start the motor after motor was stopped. The restart delay
element asserts the
RESTART DELAY OP
FlexLogic operand for
RESTART DELAY MIN TIME
after the motor stopped. The ele-
ment uses motor status asserted by the thermal model element. The thermal protection must be configured properly in
order for this function to operate.
Figure 5–116: RESTART DELAY SCHEME LOGIC
5.7.8 REDUCED VOLTAGE STARTING
PATH: SETTINGS
CONTROL ELEMENTS
REDUCED VOLTAGE STARTING
RESTART DELAY
RESTART DELAY
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
RESTART DELAY
MIN TIME: 0 s
Range: 0 to 50000 s in steps of 1
MESSAGE
RESTART DELAY BLOCK:
Off
Range: FlexLogic operand
MESSAGE
RESTART DELAY
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
RESTART DELAY
EVENTS: Disabled
Range: Disabled, Enabled
REDUCED VOLTAGE
STARTING
REDUCED VOLTAGE
STARTING: Disabled
Range: Disabled, Enabled
MESSAGE
TRANSITION MODE:
Current Only
Range: Current Only, Current or Timer,
Current and Timer
MESSAGE
REDUCED VOLT FLA:
125% FLA
Range: 25 to 300% FLA in steps of 1
MESSAGE
REDUCED VOLT TIMER:
10.0 s
Range: 1.0 to 600.0 s in steps of 0.1
MESSAGE
REDUCED VOLT BLOCK:
Off
Range: FlexLogic operand
MESSAGE
REDUCED VOLT TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
REDUCED VOLT EVENTS:
Disabled
Range: Disabled, Enabled
833017A4.CDR
SETTING
Enabled = 1
Function
Off = 0
Block
AND
FLEXLOGIC OPERAND
MOTOR OFFLINE
SETTING
= Off
Emergency Restart
restart from lockout
from the motor setup settings
SETTING
Minimum Time
0
TRESET
FLEXLOGIC OPERAND
RESTART DELAY OP
ACTUAL VALUE
Restart Delay Lockout
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...