5 SETTINGS
5.6 GROUPED ELEMENTS
5
c) THERMAL MODEL
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
MOTOR
THERMAL MODEL
THERMAL MODEL
THERMAL MODEL
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
THERMAL MODEL
CURVE: Motor
Range: Motor, Flexcurve A, Flexcurve B, Flexcurve C,
Flexcurve D, IEC
MESSAGE
THERMAL MODEL CURVE
EFFECT: Cutoff
Range: Cutoff, Shift
MESSAGE
IEC CURVE k FACTOR:
1.10
Range: 1.00 to 1.50 in steps of 0.05
MESSAGE
IEC CURVE TIME
CONSTANT: 45 min.
Range: 0 to 1000 min. in steps of 1
MESSAGE
THERMAL MODEL
TD MULTIPLIER: 1.00
Range: 0.00 to 16.00 in steps of 0.01 when thermal
model curve is Motor, otherwise 0.00 to 600.00 in
steps of 0.01
MESSAGE
UNBALANCE BIAS
K FACTOR: 0
Range: 0 to 19 in steps of 1
MESSAGE
COOL TIME CONSTANT
RUNNING: 15 min.
Range: 1 to 65000 min. in steps of 1
MESSAGE
COOL TIME CONSTANT
STOPPED: 30 min.
Range: 1 to 65000 min. in steps of 1
MESSAGE
HOT/COLD SAFE
STALL RATIO: 1.00
Range: 0.01 to 1.00 in steps of 0.01
MESSAGE
RTD BIAS:
Disabled
Range: Disabled, Enabled
MESSAGE
RTD BIAS MINIMUM
40 C
Range: 0 to 250°C in steps of 1
MESSAGE
RTD BIAS CENTER
POINT: 130 C
Range: 0 to 250°C in steps of 1
MESSAGE
RTD BIAS MAXIMUM:
155 C
Range: 0 to 250°C in steps of 1
MESSAGE
START INHIBIT
TCU MARGIN: 0%
Range: 0 to 25% in steps of 1
MESSAGE
VOLTAGE DEPENDENT
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
VOLTAGE DEPENDENT
MIN MOTOR VOLTS: 80%
Range: 60 to 99% in steps of 1
MESSAGE
VD VOLTAGE LOSS:
Off
Range: FlexLogic operand
MESSAGE
VD STALL CURRENT @
MIN V: 4.50 x FLA
Range: 1.50 to 20.00 x FLA in steps of 0.01
MESSAGE
VD SAFE STALL TIME @
MIN V: 20.0 sec.
Range: 0.1 to 1000.0 s in steps of 0.1
MESSAGE
VD ACCELL. INTERSECT
@ MIN V: 4.00 x FLA
Range: 1.50 to 20.00 x FLA in steps of 0.01
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...