5-146
M60 Motor Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
–
I
b
= Motor rated current specified by the MOTOR FULL LOAD AMPS setting.
•
THERMAL MODEL CURVE EFFECT:
This setting affects the time-to-trip thermal curves when the
THERMAL MODEL
CURVE
is selected as “Motor”. This setting takes into account the design of the machine with respect to overload capa-
bility as determined by the overload (service) factor. For motor designs where temperature rise above ambient is
based on full load current, this setting should be selected as “Cutoff”. The time to trip is then calculated using the fol-
lowing equation:
(EQ 5.10)
In the above equation, the motor stator current (
I
motor
) and motor rated current (FLA) are expressed in per units of
relay current.
For specialized motor designs where temperature rise above ambient is based on the product of the service factor and
full load current (OF × FLA), this setting should be selected as “Shifted”. The time to trip is then calculated using the
following equation:
(EQ 5.11)
In the above equation, the motor stator current (
I
motor
) and motor rated current (FLA) are expressed in per units of
relay current.
In case of uncertainty, the more conservative “Cutoff” value should be used.
The following figure illustrates the impact of this setting on the time to trip thermal curves.
Figure 5–55: IMPACT OF THE THERMAL MODEL CURVE EFFECT SETTING
•
IEC CURVE k FACTOR
: This setting applies only to the IEC motor curve and is applied as described in the
THERMAL
MODEL CURVE
setting description. Refer to the IEC 255-8 standard for additional details on its application.
trip time
TD 2.2116623
0.02530337
I
motor
FLA
--------------
1
–
2
0.05054758
I
motor
FLA
--------------
1
–
+
------------------------------------------------------------------------------------------------------------------------------------------------
=
trip time
TD 2.2116623
0.02530337
I
motor
OF FLA
-------------------------
1
–
2
0.05054758
I
motor
OF FLA
-------------------------
1
–
+
----------------------------------------------------------------------------------------------------------------------------------------------------------------------
=
1
10
100
1000
10000
0
5
8
Stator current (multiples of FLA)
SF = 1.15, EFFECT = shift
T
rip
time
(seconds)
SF = 1.15, EFFECT = cutoff
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...