![GE M60 UR Series Instruction Manual Download Page 640](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365640.webp)
F-10
M60 Motor Protection System
GE Multilin
F.2 DNP POINT LISTS
APPENDIX F
F
F.2.3 COUNTERS
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is per-
formed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.
A counter freeze command has no meaning for counters 8 and 9. M60 Digital Counter values are represented as 32-bit
integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative
counter values.
BINARY COUNTERS
Static (Steady-State) Object Number:
20
Change Event Object Number:
22
Request Function Codes supported:
1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear),
10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested:
1 (32-Bit Binary Counter with Flag)
Change Event Variation reported when variation 0 requested:
1 (32-Bit Counter Change Event without time)
Change Event Buffer Size:
10
Default Class for all points:
3
FROZEN COUNTERS
Static (Steady-State) Object Number:
21
Change Event Object Number:
23
Request Function Codes supported:
1 (read)
Static Variation reported when variation 0 requested:
1 (32-Bit Frozen Counter with Flag)
Change Event Variation reported when variation 0 requested:
1 (32-Bit Frozen Counter Event without time)
Change Event Buffer Size:
10
Default Class for all points:
3
Table F–4: BINARY AND FROZEN COUNTERS
POINT
INDEX
NAME/DESCRIPTION
0
Digital Counter 1
1
Digital Counter 2
2
Digital Counter 3
3
Digital Counter 4
4
Digital Counter 5
5
Digital Counter 6
6
Digital Counter 7
7
Digital Counter 8
8
Oscillography Trigger Count
9
Events Since Last Clear
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...