M60 Motor Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
•
VD STALL CURRENT @ 100% V
: This setting defines the locked rotor current level at the rated motor voltage (
I
3
).
•
VD SAFE STALL TIME @ 100% V
: This setting defines the maximum time the motor is allowed to withstand the
locked rotor current at rated motor voltage (
t
3
).
•
VD ACCEL. INTERESECT @ 100% V
: This setting defines the starting current level corresponding to the crossing
point between the acceleration thermal limit at rated voltage and the programmed relay overload curve (
I
4
). This value
can be typically determined from the motor acceleration curves. The current value at the breakdown torque for the
100% voltage start is recommended for this setting.
The voltage dependent overload curves are shown below.
Figure 5–62: VOLTAGE DEPENDENT OVERLOAD CURVES
1.00
10.00
100.00
1000.00
10000.00
0
1
2
3
4
5
6
7
8
PER UNIT CURRENT
TIME
T
O
TR
IP
(SEC
ON
D
S
)
THERMAL MODEL CUR
V
E
LOCKED ROTOR LINE
MIN
V
ACCELERATE
100% ACCELERATE
110% ACCELERATE
MIN
V
LINE
100%
V
LINE
110%
V
LINE
THERMAL MODEL CURVE
ACCELERATION INTERSECT@ minV (2)
ACCELERATION INTERSECT@ 100%V (4)
ACCELERATION INTERSECT@ 110%V (6)
SAFE STALL POINT @ minV (1)
SAFE STALL POINT @ 100%V (3)
SAFE STALL POINT @ 110%V (5)
LOCKED ROTOR THERMAL LIMIT CURVE
THERMAL LIMIT CURVES
FOR ABNORMAL CONDITIONS:
- LESS THAN Vmin
(A)
- MORE THAN 110%V
(B)
- LOSS OF VOLTAGE
(C)
A
B
C
833715A1.CDR
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...