E-8
M60 Motor Protection System
GE Multilin
E.1 IEC 60870-5-104 PROTOCOL
APPENDIX E
E
Counter freeze with reset
Counter reset
General request counter
Request counter group 1
Request counter group 2
Request counter group 3
Request counter group 4
Parameter loading:
Threshold value
Smoothing factor
Low limit for transmission of measured values
High limit for transmission of measured values
Parameter activation:
Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
Test procedure
File transfer:
File transfer in monitor direction:
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analog values
File transfer in control direction:
Transparent file
Background scan:
Background scan
Acquisition of transmission delay:
Acquisition of transmission delay
Definition of time outs:
Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s
Maximum number of outstanding I-format APDUs
k
and latest acknowledge APDUs (
w
):
PARAMETER
DEFAULT
VALUE
REMARKS
SELECTED
VALUE
t
0
30 s
Timeout of connection establishment
120 s
t
1
15 s
Timeout of send or test APDUs
15 s
t
2
10 s
Timeout for acknowledgements in case of no data messages
t
2
<
t
1
10 s
t
3
20 s
Timeout for sending test frames in case of a long idle state
20 s
PARAMETER
DEFAULT
VALUE
REMARKS
SELECTED
VALUE
k
12 APDUs
Maximum difference receive sequence number to send state variable
12 APDUs
w
8 APDUs
Latest acknowledge after receiving
w
I-format APDUs
8 APDUs
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...