![GE M60 UR Series Instruction Manual Download Page 518](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365518.webp)
B-44
M60 Motor Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
7DD0
...Repeated for User Programmable Pushbutton 14
7E00
...Repeated for User Programmable Pushbutton 15
7E30
...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 Modules)
7F00
Neutral Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F01
Neutral Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F02
Neutral Overvoltage 1 Pickup
0 to 3.00
pu
0.001
F001
300
7F03
Neutral Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7F04
Neutral Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7F05
Neutral Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7F07
Neutral Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F08
Neutral Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F09
Neutral Overvoltage 1 Curves
0 to 3
---
1
F116
0 (Definite Time)
7F0A
Reserved (8 items)
0 to 65535
---
1
F001
0
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 Modules)
7F60
Auxiliary Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F61
Auxiliary Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F62
Auxiliary Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
700
7F63
Auxiliary Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7F64
Auxiliary Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7F65
Auxiliary Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7F66
Auxiliary Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7F68
Auxiliary Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F69
Auxiliary Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F6A
Reserved (7 items)
0 to 65535
---
1
F001
0
7F71
...Repeated for Auxiliary Undervoltage 2
7F82
...Repeated for Auxiliary Undervoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 Modules)
7FA0
Auxiliary Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7FA1
Auxiliary Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7FA2
Auxiliary Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
300
7FA3
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7FA4
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7FA5
Auxiliary Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7FA7
Auxiliary Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7FA8
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7FA9
Reserved (8 items)
0 to 65535
---
1
F001
0
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
2 to 90
Hz
---
F001
0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
-55 to 125
C
1
F002
-55
81C1
Reserved Register T2
-55 to 125
C
1
F002
125
81C2
Reserved Register T3
-2147483647 to
2147483647
---
1
F004
0
81C4
Reserved Register T4
0 to 4294967295
---
1
F003
0
81C6
Reserved Register T5
0 to 4294967295
---
1
F003
0
81C8
Reserved Register T6
0 to 4294967295
---
1
F003
0
81CA
Reserved Register T7
0 to 4294967295
---
1
F003
0
Table B–9: MODBUS MEMORY MAP (Sheet 37 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...