5.7 CONTROL ELEMENTS
5
5.7.7 MOTOR START SUPERVISION
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
START SUPERVISION
The motor start supervision feature consists of three elements that guard against excessive starting duty. These elements
are in addition to the start inhibit that could be imposed by the thermal model. A method to prevent starting is by wiring an
M60 output contact actuated by motor start supervision elements in the motor energizing control circuit. The output contact
changes state only when the motor is stopped to accommodate control circuits that must be continuously energized such
as a contactor.
The three elements of motor start supervision are:
1.
Maximum starting rate (starts per hour):
This element defines the number of starts attempts allowed in a program-
mable time interval. Only the number of re-start attempts during the interval is controlled and not the time in between.
The latter is controlled by the time between starts element. When the motor is stopped after the last allowed start the
energizing or closing control circuit is disabled until the end of the defined interval. Every start initiate a new interval in
which the start number is limited A typical starting frequency is three starts per hour.
2.
Time between starts:
This function enforces a programmable minimum time duration between two successive starts
attempts. A time delay is initiated with every start and if the motor is stopped a restart is not allowed until the specified
interval has lapsed.
3.
Restart Delay:
The restart delay function defines a programmable delay after a motor has stopped before it can be
started again. It allows load interruption transient conditions such as down-hole pump applications where gravitational
force causes reverse rotation to subside. Starting when the load is reversing could cause damage to the motor or
pump.
START SUPERVISION
MAXIMUM STARTING
RATE (STARTS/HR)
MESSAGE
TIME BETWEEN
STARTS
MESSAGE
RESTART DELAY
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...