GE Multilin
M60 Motor Protection System
B-17
APPENDIX B
B.4 MEMORY MAPPING
B
1D40
...Repeated for Source 5
1D50
...Repeated for Source 6
Energy Commands (Read/Write Command)
1D60
Energy Clear Command
0 to 1
---
1
F126
0 (No)
Source Frequency (Read Only) (6 Modules)
1D80
Frequency for Source 1
2 to 90
Hz
0.001
F003
0
1D82
Frequency for Source 2
2 to 90
Hz
0.001
F003
0
1D84
Frequency for Source 3
2 to 90
Hz
0.001
F003
0
1D86
Frequency for Source 4
2 to 90
Hz
0.001
F003
0
1D88
Frequency for Source 5
2 to 90
Hz
0.001
F003
0
1D8A
Frequency for Source 6
2 to 90
Hz
0.001
F003
0
Breaker Flashover (Read/Write Setting) (2 Modules)
2196
Breaker Flashover 1 Function
0 to 1
---
1
F102
0 (Disabled)
2197
Breaker Flashover 1 Side 1 Source
0 to 5
---
1
F167
0 (SRC 1)
2198
Breaker Flashover 1 Side 2 Source
0 to 6
---
1
F211
0 (None)
2199
Breaker Flashover 1 Status Closed A
0 to 4294967295
---
1
F300
0
219B
Breaker Flashover 1 Status Closed B
0 to 4294967295
---
1
F300
0
219D
Breaker Flashover 1 Status Closed C
0 to 4294967295
---
1
F300
0
219F
Breaker Flashover 1 Voltage Pickup Level
0 to 1.5
pu
0.001
F001
850
21A0
Breaker Flashover 1 Voltage Difference Pickup Level
0 to 100000
V
1
F060
1000
21A2
Breaker Flashover 1 Current Pickup Level
0 to 1.5
pu
0.001
F001
600
21A3
Breaker Flashover 1 Pickup Delay
0 to 65.535
s
0.001
F001
100
21A4
Breaker Flashover 1 Supervision Phase A
0 to 4294967295
---
1
F300
0
21A6
Breaker Flashover 1 Supervision Phase B
0 to 4294967295
---
1
F300
0
21A8
Breaker Flashover 1 Supervision Phase C
0 to 4294967295
---
1
F300
0
21AA
Breaker Flashover 1 Block
0 to 4294967295
---
1
F300
0
21AC
Breaker Flashover 1 Events
0 to 1
---
1
F102
0 (Disabled)
21AD
Breaker Flashover 1 Target
0 to 2
---
1
F109
0 (Self-Reset)
21AE
Reserved (4 items)
---
---
---
F001
0
21B2
...Repeated for breaker flashover 2
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
0 to 1
---
1
F126
0 (No)
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
0 to 7
---
1
F244
6 (H1a)
2461
Field Raw Data Freeze
0 to 1
---
1
F102
0 (Disabled)
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 Modules)
2540
Remote Double-point Status Input 1 Device
1 to 32
---
1
F001
1
2541
Remote Double-point Status Input 1 Item
0 to 64
---
1
F606
0 (None)
2542
Remote Double-point Status Input 1 Name
1 to 64
---
1
F205
"RemDPS Ip 1"
2548
Remote Double-point Status Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
2549
... Repeated for double-point status input 2
2552
... Repeated for double-point status input 3
255B
... Repeated for double-point status input 4
2564
... Repeated for double-point status input 5
IEC 61850 GGIO5 Configuration (Read/Write Setting Registers) (16 Modules)
26D0
IEC 61850 GGIO5 uinteger Input 1 Operand
---
---
---
F612
0
26D1
IEC 61850 GGIO5 uinteger Input 2 Operand
---
---
---
F612
0
26D2
IEC 61850 GGIO5 uinteger Input 3 Operand
---
---
---
F612
0
26D3
IEC 61850 GGIO5 uinteger Input 4 Operand
---
---
---
F612
0
26D4
IEC 61850 GGIO5 uinteger Input 5 Operand
---
---
---
F612
0
26D5
IEC 61850 GGIO5 uinteger Input 6 Operand
---
---
---
F612
0
26D6
IEC 61850 GGIO5 uinteger Input 7 Operand
---
---
---
F612
0
26D7
IEC 61850 GGIO5 uinteger Input 8 Operand
---
---
---
F612
0
26D8
IEC 61850 GGIO5 uinteger Input 9 Operand
---
---
---
F612
0
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...