GE Multilin
M60 Motor Protection System
5-275
5 SETTINGS
5.9 TRANSDUCER INPUTS AND OUTPUTS
5
Figure 5–136: REMOTE RTD INPUT PROTECTION LOGIC
5.9.4 DCMA OUTPUTS
PATH: SETTINGS
TRANSDUCER I/O
DCMA OUTPUTS
DCMA OUTPUT H1(W8)
Hardware and software is provided to generate dcmA signals that allow interfacing with external equipment. Specific hard-
ware details are contained in chapter 3. The dcmA output channels are arranged in a manner similar to transducer input or
CT and VT channels. The user configures individual channels with the settings shown below.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an exam-
ple for channel M5 is shown).
The relay checks the driving signal (
x
in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as
MIN VAL
and
MAX VAL
match the output range of the hardware defined as
RANGE
. The follow-
ing equation is applied:
(EQ 5.50)
DCMA OUTPUT H1
DCMA OUTPUT H1
SOURCE: Off
Range: Off, any analog actual value parameter
MESSAGE
DCMA OUTPUT H1
RANGE: –1 to 1 mA
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
MESSAGE
DCMA OUTPUT H1
MIN VAL: 0.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
DCMA OUTPUT H1
MAX VAL: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
None
Alarm
Block
From other remote
RTDs for voting
To other remote RTDs
for voting
SETTINGS
Enabled = 1
Function
Off = 0
Block
AND
= RRTD 1
ID
SETTING
SETTING
Open
RUN
R > 1000 ohms
RUN
T
–40°C
£
OR
AND
SETTINGS
Trip Temperature
RUN
temperature > Trip Pickup
Alarm Temperature
RUN
temperature > Alarm Pickup
SETTINGS
Trip Pickup Delay
Trip Reset Delay
T
PKP
0
T
PKP
T
DPO
Alarm Pickup Delay
SETTINGS
Application
Voting logic
Trip Voting
FLEXLOGIC OPERANDS
RRTD 1 ALARM OP
RRTD 1 TRIP PKP
RRTD 1 TRIP DPO
RRTD 1 SHORTED
RRTD 1 ALARM PKP
RRTD 1 ALARM DPO
RRTD 1 OPEN
FLEXLOGIC OPERAND
REMOTE RTD 1 TRIP OP
833026A1.CDR
Type
Temperature read
from RRTD
SETTING
I
out
I
min
if
x
MIN VAL
I
max
if
x
MAX VAL
k x
MIN VAL
–
I
min
+
otherwise
=
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...