GE Multilin
M60 Motor Protection System
5-127
5 SETTINGS
5.5 FLEXLOGIC
5
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic are listed in the Flex-
Logic operators table.
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
Reset command is operated (set by all three operands below).
Communications source of the reset command.
Operand (assigned in the
INPUTS/OUTPUTS
RESETTING
menu) source
of the reset command.
Reset key (pushbutton) source of the reset command.
SELF-
DIAGNOSTICS
(See
Relay Self-
tests
descriptions in
Chapter 7:
Commands and
Targets)
ANY MAJOR ERROR
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
CLOCK UNSYNCHRONIZED
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
FLEXLOGIC ERR TOKEN
LATCHING OUT ERROR
MAINTENANCE ALERT
FIRST ETHERNET FAIL
PROCESS BUS FAILURE
PTP FAILURE
REMOTE DEVICE OFF
RRTD COMM FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
The battery is not functioning. Return power supply module to manufacturer.
Relay is not synchronized to the international time standard
A direct device is configured but not connected
The Direct I/O settings is for a connection that is not in a ring
The configuration of modules does not match the stored order code
A FlexLogic equation is incorrect
A difference is detected between the desired and actual latch contact state
A subset of the minor self-test errors generated, see Chapter 7
Link failure detected. See description in
Chapter 7: Commands and targets.
See description in
Chapter 7: Commands and targets
"Bad PTP Signal" self-test as described in Chapter 7
One or more GOOSE devices are not responding
See description in
Chapter 7: Commands and targets
See description in
Chapter 7: Commands and targets
See description in
Chapter 7: Commands and targets
SNTP server is not responding
See description in
Chapter 7: Commands and targets
Monitors ambient temperature and maximum operating temperature
The product setup>installation>relay settings setting is not programmed
TEMPERATURE
MONITOR
TEMP MONITOR
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
USER-
PROGRAMMABLE
PUSHBUTTONS
PUSHBUTTON 1 ON
PUSHBUTTON 1 OFF
ANY PB ON
Pushbutton number 1 is in the “On” position
Pushbutton number 1 is in the “Off” position
Any of twelve pushbuttons is in the “On” position
PUSHBUTTON 2 to 12
Same set of operands as PUSHBUTTON 1
Table 5–15: FLEXLOGIC GATE CHARACTERISTICS
GATES
NUMBER OF INPUTS
OUTPUT IS ‘1’ (= ON) IF...
NOT
1
input is ‘0’
OR
2 to 16
any input is ‘1’
AND
2 to 16
all inputs are ‘1’
NOR
2 to 16
all inputs are ‘0’
NAND
2 to 16
any input is ‘0’
XOR
2
only one input is ‘1’
Table 5–14: M60 FLEXLOGIC OPERANDS (Sheet 8 of 8)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...