GE Multilin
M60 Motor Protection System
B-43
APPENDIX B
B.4 MEMORY MAPPING
B
7B26
VD Overload Acceleration Intersect at Minimum Volts
1.5 to 20
FLA
0.01
F001
400
7B27
VD Overload Stall Current at 100% Voltage
1.5 to 20
FLA
0.01
F001
600
7B28
VD Overload Safe Stall Time at 100% Voltage
0.1 to 1000
s
0.1
F001
100
7B29
VD Overload Acceleration Intersect at 100% Voltage
1.5 to 20
FLA
0.01
F001
500
7B2A
Speed 2 Voltage Dependent Overload Function
0 to 1
---
1
F102
0 (Disabled)
7B2B
Speed 2 VD Overload Minimum Motor Volts
60 to 99
%
1
F001
80
7B2C
Speed 2 Voltage Dependent Overload Voltage Loss
0 to 4294967295
---
1
F300
0
7B2E
Speed 2 VD Overload Stall Current at Minimum Volts
1.5 to 20
FLA
0.01
F001
450
7B2F
Speed 2 VD Overload Safe Stall Time at Minimum Volts
0.1 to 1000
s
0.1
F001
200
7B30
Speed 2 VD Acceleration Intersect at Minimum Volts
1.5 to 20
FLA
0.01
F001
400
7B31
Speed 2 VD Overload Stall Current at 100% Voltage
1.5 to 20
FLA
0.01
F001
600
7B32
Speed 2 VD Overload Safe Stall Time at 100% Voltage
0.1 to 1000
s
0.1
F001
100
7B33
Speed 2 VD Acceleration Intersect at 100% Voltage
1.5 to 20
FLA
0.01
F001
500
Motor Acceleration Time (Read/Write Grouped Setting)
7B40
Motor Acceleration Function
0 to 1
---
1
F102
0 (Disabled)
7B41
Motor Acceleration Current
1.00 to 10.00
FLA
0.01
F001
600
7B42
Motor Acceleration Time
0.05 to 180.00
s
0.01
F001
1000
7B43
Motor Acceleration Mode
0 to 1
---
1
F097
0 (Definite Time)
7B44
Motor Acceleration Block
0 to 4294967295
---
1
F300
0
7B45
Motor Acceleration Target
0 to 2
---
1
F109
0 (Self-reset)
7B46
Motor Acceleration Events
0 to 1
---
1
F102
0 (Disabled)
7B47
Speed 2 Motor Acceleration Current
1.00 to 10.00
x FLA
0.01
F001
600
7B48
Speed 2 Motor Acceleration Time
0.05 to 180.00
s
0.01
F001
1000
7B49
Speed 2 Motor Acceleration Mode
0 to 1
---
1
F097
0 (Definite Time)
7B4B
Speed 2 Motor Acceleration Speed 1-2
0.05 to 180.00
s
0.01
F001
1000
7B4C
Speed 2 Motor Acceleration Block
0 to 4294967295
---
1
F300
0
7B4E
Reserved (9 items)
---
---
---
F001
0
User Programmable Pushbuttons (Read/Write Setting) (16 Modules)
7B60
User Programmable Pushbutton 1 Function
0 to 2
---
1
F137
0 (Disabled)
7B61
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
7B6B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
7B75
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
7B7F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
7B80
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
7B82
User Programmable Pushbutton 1 LED Operand
0 to 4294967295
---
1
F300
0
7B84
User Programmable Pushbutton 1 Autoreset Delay
0 to 600
s
0.05
F001
0
7B85
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
7B86
User Programmable Pushbutton 1 Local Lock
0 to 4294967295
---
1
F300
0
7B88
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
7B89
User Programmable Pushbutton 1 Remote Lock
0 to 4294967295
---
1
F300
0
7B8B
User Programmable Pushbutton 1 Reset
0 to 4294967295
---
1
F300
0
7B8D
User Programmable Pushbutton 1 Set
0 to 4294967295
---
1
F300
0
7B8F
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
7B90
...Repeated for User Programmable Pushbutton 2
7BC0
...Repeated for User Programmable Pushbutton 3
7BF0
...Repeated for User Programmable Pushbutton 4
7C20
...Repeated for User Programmable Pushbutton 5
7C50
...Repeated for User Programmable Pushbutton 6
7C80
...Repeated for User Programmable Pushbutton 7
7CB0
...Repeated for User Programmable Pushbutton 8
7DE0
...Repeated for User Programmable Pushbutton 9
7D10
...Repeated for User Programmable Pushbutton 10
7D40
...Repeated for User Programmable Pushbutton 11
Table B–9: MODBUS MEMORY MAP (Sheet 36 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...