![GE M60 UR Series Instruction Manual Download Page 514](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365514.webp)
B-40
M60 Motor Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
6956
Mechanical Jam Target
0 to 2
---
1
F109
0 (Self-reset)
6957
Mechanical Jam Events
0 to 1
---
1
F102
0 (Disabled)
6958
Reserved (8 items)
---
---
---
F001
0
Motor Learned Data (Read/Write Setting)
6960
Motor Learned Data Starts to Learn
1 to 5
---
1
F102
1
6961
Motor Learned Data Calculation Period
1 to 90
minutes
1
F001
15
6962
Reserved
---
---
---
F001
0
Motor Learned Data (Read Only Actual Values)
6963
Motor Learned Data Records Number
0 to 250
---
1
F001
0
6964
Motor Learned Data Last Cleared Date
0 to 4294967295
---
---
F050
0
6966
Motor Learned Data Acceleration Time
0 to 655.35
s
0.01
F001
0
6967
Motor Learned Data Starting Current
0.00 to 40.00
× FLA
0.01
F001
0
6968
Motor Learned Data Thermal Capacity Used
0 to 65535
%
1
F001
0
6969
Motor Learned Data Motor Load
0.00 to 40.00
× FLA
0.01
F001
0
696A
Motor Learned Data Run Time After Start
0 to 4294967295
---
---
F050
0
696C
Reserved
---
---
---
F001
0
Phase Undervoltage (Read/Write Grouped Setting) (3 Modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7008
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7009
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
700A
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to
Ground)
700B
Reserved (6 items)
0 to 1
---
1
F001
0
7011
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7047
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7048
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7049
...Repeated for Phase Overvoltage 2
7052
...Repeated for Phase Overvoltage 3
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 Modules)
7200
Phase Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7201
Phase Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7202
Phase Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
7204
Phase Directional Overcurrent 1 ECA
0 to 359
---
1
F001
30
7205
Phase Directional Overcurrent 1 Pol V Threshold
0 to 3
pu
0.001
F001
700
7206
Phase Directional Overcurrent 1 Block Overcurrent
0 to 1
---
1
F126
0 (No)
7207
Phase Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7208
Phase Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
7209
Reserved (8 items)
0 to 1
---
1
F001
0
7211
...Repeated for Phase Directional Overcurrent 2
Table B–9: MODBUS MEMORY MAP (Sheet 33 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...