5-276
M60 Motor Protection System
GE Multilin
5.9 TRANSDUCER INPUTS AND OUTPUTS
5 SETTINGS
5
where:
x
is a driving signal specified by the
SOURCE
setting
I
min
and
I
max
are defined by the
RANGE
setting
k
is a scaling constant calculated as:
(EQ 5.51)
The feature is intentionally inhibited if the
MAX VAL
and
MIN VAL
settings are entered incorrectly, e.g. when
MAX VAL
–
MIN
VAL
< 0.1 pu. The resulting characteristic is illustrated in the following figure.
Figure 5–137: DCMA OUTPUT CHARACTERISTIC
The dcmA output settings are described below.
•
DCMA OUTPUT H1 SOURCE
: This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving dcmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters.
•
DCMA OUTPUT H1 RANGE
: This setting allows selection of the output range. Each dcmA channel may be set inde-
pendently to work with different ranges. The three most commonly used output ranges are available.
•
DCMA OUTPUT H1 MIN VAL
: This setting allows setting the minimum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement base units.
•
DCMA OUTPUT H1 MAX VAL
: This setting allows setting the maximum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement base units.
The
DCMA OUTPUT H1 MIN VAL
and
DCMA OUTPUT H1 MAX VAL
settings are ignored for power factor base units (i.e. if
the
DCMA OUTPUT H1 SOURCE
is set to FlexAnalog value based on power factor measurement).
Three application examples are described below.
EXAMPLE: POWER MONITORING
A three phase active power on a 13.8 kV system measured via UR-series relay source 1 is to be monitored by the dcmA H1
output of the range of –1 to 1 mA. The following settings are applied on the relay: CT ratio = 1200:5, VT secondary 115, VT
connection is delta, and VT ratio = 120. The nominal current is 800 A primary and the nominal power factor is 0.90. The
power is to be monitored in both importing and exporting directions and allow for 20% overload compared to the nominal.
The nominal three-phase power is:
(EQ 5.52)
The three-phase power with 20% overload margin is:
(EQ 5.53)
k
I
max
I
min
–
MAX VAL
MIN VAL
–
-------------------------------------------------
=
842739A1.CDR
DRIVING SIGNAL
OUTPUT CURRENT
MIN VAL
I
min
I
max
MAX VAL
NOTE
P
3 13.8 kV 0.8 kA
0.9
17.21 MW
=
=
P
max
1.2 17.21 MW
20.65 MW
=
=
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...