5-200
M60 Motor Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
When the scheme is initiated, it immediately sends a trip signal to the breaker initially signaled to trip (this feature is usually
described as re-trip). This reduces the possibility of widespread tripping that results from a declaration of a failed breaker.
DETERMINATION OF A BREAKER FAILURE CONDITION:
The schemes determine a breaker failure condition via three
paths
. Each of these paths is equipped with a time delay, after
which a failed breaker is declared and trip signals are sent to all breakers required to clear the zone. The delayed paths are
associated with breaker failure timers 1, 2, and 3, which are intended to have delays increasing with increasing timer num-
bers. These delayed paths are individually enabled to allow for maximum flexibility.
Timer 1 logic (early path) is supervised by a fast-operating breaker auxiliary contact. If the breaker is still closed (as indi-
cated by the auxiliary contact) and fault current is detected after the delay interval, an output is issued. Operation of the
breaker auxiliary switch indicates that the breaker has mechanically operated. The continued presence of current indicates
that the breaker has failed to interrupt the circuit.
Timer 2 logic (main path) is not supervised by a breaker auxiliary contact. If fault current is detected after the delay interval,
an output is issued. This path is intended to detect a breaker that opens mechanically but fails to interrupt fault current; the
logic therefore does not use a breaker auxiliary contact.
The timer 1 and 2 paths provide two levels of current supervision, high-set and low-set, that allow the supervision level to
change from a current which flows before a breaker inserts an opening resistor into the faulted circuit to a lower level after
resistor insertion. The high-set detector is enabled after timeout of timer 1 or 2, along with a timer that will enable the low-
set detector after its delay interval. The delay interval between high-set and low-set is the expected breaker opening time.
Both current detectors provide a fast operating time for currents at small multiples of the pickup value. The overcurrent
detectors are required to operate after the breaker failure delay interval to eliminate the need for very fast resetting overcur-
rent detectors.
Timer 3 logic (slow path) is supervised by a breaker auxiliary contact and a control switch contact used to indicate that the
breaker is in or out-of-service, disabling this path when the breaker is out-of-service for maintenance. There is no current
level check in this logic as it is intended to detect low magnitude faults and it is therefore the slowest to operate.
OUTPUT:
The outputs from the schemes are:
•
FlexLogic operands that report on the operation of portions of the scheme
•
FlexLogic operand used to re-trip the protected breaker
•
FlexLogic operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an
adjustable period.
•
Target message indicating a failed breaker has been declared
•
Illumination of the faceplate Trip LED (and the Phase A, B or C LED, if applicable)
MAIN PATH SEQUENCE:
Figure 5–93: BREAKER FAILURE MAIN PATH SEQUENCE
PROTECTION OPERATION
BREAKER INTERRUPTING TIME
CALCULATED CURRENT MAGNITUDE
ACTUAL CURRENT MAGNITUDE
FAILED INTERRUPTION
CORRECT INTERRUPTION
Rampdown
(ASSUMED 1.5 cycles)
INITIATE (1/8 cycle)
BREAKER FAILURE TIMER No. 2 (±1/8 cycle)
BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle)
BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle)
FAULT
OCCURS
1
2
3
4
5
6
7
8
9
10
11
0
0
0
AMP
(ASSUMED 3 cycles)
cycles
827083A
6
.CDR
MARGIN
(Assumed 2 Cycles)
BACKUP BREAKER OPERATING TIME
(Assumed 3 Cycles)
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...