![GE M60 UR Series Instruction Manual Download Page 510](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365510.webp)
B-36
M60 Motor Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5D04
Ground Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5D05
Ground Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5D06
Ground Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5D07
Ground Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5D09
Ground Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5D0A
Ground Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5D0B
Reserved (6 items)
0 to 1
---
1
F001
0
5D11
...Repeated for Ground Time Overcurrent 2
5D22
...Repeated for Ground Time Overcurrent 3
5D33
...Repeated for Ground Time Overcurrent 4
5D44
...Repeated for Ground Time Overcurrent 5
5D55
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (up to 12 Modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5DA2
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5DA3
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5DA5
Ground Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5DA7
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5DA8
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5DA9
Reserved (8 items)
0 to 1
---
1
F001
0
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
5DE4
...Repeated for Ground Instantaneous Overcurrent 5
5DF5
...Repeated for Ground Instantaneous Overcurrent 6
5E06
...Repeated for Ground Instantaneous Overcurrent 7
5E17
...Repeated for Ground Instantaneous Overcurrent 8
5E28
...Repeated for Ground Instantaneous Overcurrent 9
5E39
...Repeated for Ground Instantaneous Overcurrent 10
5E4A
...Repeated for Ground Instantaneous Overcurrent 11
5E5B
...Repeated for Ground Instantaneous Overcurrent 12
CT Fail (Read/Write Setting) (6 Modules)
5E6C
CT Fail 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E6D
CT Fail 1 Block
0 to 4294967295
---
1
F300
0
5E6F
CT Fail 1 Current Source 1
0 to 5
---
1
F167
0 (SRC 1)
5E70
CT Fail 1 Current Pickup 1
0 to 2
pu
0.1
F001
2
5E71
CT Fail 1 Current Source 2
0 to 5
---
1
F167
1 (SRC 2)
5E72
CT Fail 1 Current Pickup 2
0 to 2
pu
0.1
F001
2
5E73
CT Fail 1 Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
5E74
CT Fail 1 Voltage Pickup
0 to 2
pu
0.01
F001
20
5E75
CT Fail 1 Pickup Delay
0 to 65.535
s
0.001
F001
1000
5E76
CT Fail 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5E77
CT Fail 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E78
...Repeated for CT Fail 2
5E84
...Repeated for CT Fail 3
5E90
...Repeated for CT Fail 4
5E9C
...Repeated for CT Fail 5
5EA8
...Repeated for CT Fail 6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic to Activate Groups 2 through 6 (5 items)
0 to 4294967295
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...