![GE M60 UR Series Instruction Manual Download Page 269](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365269.webp)
GE Multilin
M60 Motor Protection System
5-141
5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6.3 MOTOR
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
MOTOR
b) ACCELERATION TIME
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
MOTOR
ACCELERATION TIME
Many motors have quite a time margin between acceleration-time and the stall limit. It is advantageous to detect stalling
during a start as early as possible to minimize re-starting delays once the cause of the stall is remedied, e.g. neglecting to
release a fan brake.
The acceleration time element compares actual starting time with a pre-determined time setting and operates when it is
exceeded. This element has the functionality to adapt the tripping time for starts with lower starting current, and it stores
acceleration time and current of the last five starts. The element uses currents configured under
SYSTEM SETUP
MOTOR
MOTOR LINE SOURCE
and motor status asserted by the thermal model element. Both the signal source and thermal pro-
tection must be configured properly in order for the acceleration time protection to operate.
The figure below shows examples of constant and variable acceleration currents and explains measurement of the acceler-
ation time and current. Part A represents a constant current start and part B represents a variable current start.
MOTOR
ACCELERATION
TIME
MESSAGE
THERMAL MODEL
MESSAGE
AMP UNBALANCE 1
MESSAGE
AMP UNBALANCE 2
MESSAGE
UNDERCURRENT
MESSAGE
MECHANICAL JAM
MESSAGE
TWO-SPEED MOTOR
ACCELERATION TIME
ACCELERATION
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
ACCELERATION
CURRENT: 6.00 x FLC
Range: 1.00 to 10.00 x FLC in steps of 0.01
MESSAGE
ACCELERATION TIME:
10.00 s
Range: 0.50 to 180.00 s in steps of 0.01
MESSAGE
ACCELERATION MODE:
Definite Time
Range: Definite Time, Adaptive
MESSAGE
ACCELERATION BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
ACCLERATION TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
ACCLERATION EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...