GE Multilin
M60 Motor Protection System
5-15
5 SETTINGS
5.2 PRODUCT SETUP
5
4.
Click
OK
to save the changes.
f) CYBERSENTRY SECURITY
The EnerVista software provides the means to configure and authenticate UR using either server or device or authentica-
tion. Access to various functionality depends on user role.
The login screen of EnerVista has two options for access to the UR, server and device authentication.
Figure 5–2: LOGIN SCREEN FOR CYBERSENTRY
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
When the "Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authen-
ticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer) as login
accounts and the associated passwords are stored on the UR device. In this case, access is not user-attributable. In cases
where user-attributable access is required, especially for auditable processes for compliance reasons, use server authenti-
cation (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.
Event Recorder
Allows the user to use the digital fault recorder
FlexLogic
Allows the user to read FlexLogic values
Update Info
Allows the user to write to any function to which they have read privileges. When any of the Settings, Event
Recorder, and FlexLogic check boxes are enabled by themselves, the user is granted read access. When
any of them are enabled in conjunction with the Update Info box, they are granted read and write access.
The user is not granted write access to functions that are not checked, even if the Update Info field is
checked.
Admin
The user is an EnerVista UR Setup administrator, therefore receiving all of the administrative rights.
Exercise caution when granting administrator rights.
Table 5–2: ACCESS RIGHTS SUMMARY
FIELD
DESCRIPTION
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...