![GE M60 UR Series Instruction Manual Download Page 56](http://html.mh-extra.com/html/ge/m60-ur-series/m60-ur-series_instruction-manual_130365056.webp)
2-26
M60 Motor Protection System
GE Multilin
2.3 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
TYPICAL LINK DISTANCE
Compensated difference in transmitting and receiving (channel
asymmetry) channel delays using GPS satellite clock: 10 ms
2.3.10 ENVIRONMENTAL
AMBIENT TEMPERATURES
Storage temperature:
–40 to 85°C
Operating temperature: –40 to 60°C; the LCD contrast can be
impaired at temperatures less than –
20°C
HUMIDITY
Humidity:
operating up to 95% (non-condensing) at
55°C (as per IEC60068-2-30 variant 1, 6
days).
OTHER
Altitude:
2000 m (maximum)
Pollution degree:
II
Overvoltage category:
II
Ingress protection:
IP20 front, IP10 back
EMITTER TYPE
CABLE
TYPE
CONNECTOR
TYPE
TYPICAL
DISTANCE
820 nm LED,
multimode
62.5/125
μ
m
ST
1.65 km
1300 nm LED,
multimode
62.5/125
μ
m
ST
3.8 km
1300 nm ELED,
single mode
9/125
μ
m
ST
11.4 km
1300 nm Laser,
single mode
9/125
μ
m
ST
64 km
1550 nm Laser,
single mode
9/125
μ
m
ST
105 km
Typical distances listed are based on the follow-
ing assumptions for system loss. As actual losses
vary from one installation to another, the distance
covered by your system may vary.
CONNECTOR LOSSES (TOTAL OF BOTH ENDS)
ST connector
2 dB
FIBER LOSSES
820 nm multimode
3 dB/km
1300 nm multimode
1 dB/km
1300 nm single mode
0.35 dB/km
1550 nm single mode
0.25 dB/km
Splice losses:
One splice every 2 km,
at 0.05 dB loss per splice.
SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for
all other losses.
NOTE
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...