GE Multilin
M60 Motor Protection System
B-15
APPENDIX B
B.4 MEMORY MAPPING
B
16D0
...Repeated for module number 5
16D2
...Repeated for module number 6
16D4
...Repeated for module number 7
16D6
...Repeated for module number 8
Source Current (Read Only) (6 Modules)
1800
Source 1 Phase A Current RMS
0 to 999999.999
A
0.001
F060
0
1802
Source 1 Phase B Current RMS
0 to 999999.999
A
0.001
F060
0
1804
Source 1 Phase C Current RMS
0 to 999999.999
A
0.001
F060
0
1806
Source 1 Neutral Current RMS
0 to 999999.999
A
0.001
F060
0
1808
Source 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
180A
Source 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
180B
Source 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
180D
Source 1 Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
180E
Source 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
1810
Source 1 Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
1811
Source 1 Neutral Current Magnitude
0 to 999999.999
A
0.001
F060
0
1813
Source 1 Neutral Current Angle
-359.9 to 0
degrees
0.1
F002
0
1814
Source 1 Ground Current RMS
0 to 999999.999
A
0.001
F060
0
1816
Source 1 Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1818
Source 1 Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1819
Source 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181B
Source 1 Zero Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181C
Source 1 Positive Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181E
Source 1 Positive Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181F
Source 1 Negative Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
1821
Source 1 Negative Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
1822
Source 1 Differential Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1824
Source 1 Differential Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1825
Reserved (27 items)
---
---
---
F001
0
1840
...Repeated for Source 2
1880
...Repeated for Source 3
18C0
...Repeated for Source 4
1900
...Repeated for Source 5
1940
...Repeated for Source 6
Source Voltage (Read Only) (6 Modules)
1A00
Source 1 Phase AG Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A02
Source 1 Phase BG Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A04
Source 1 Phase CG Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A06
Source 1 Phase AG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A08
Source 1 Phase AG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A09
Source 1 Phase BG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0B
Source 1 Phase BG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0C
Source 1 Phase CG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0E
Source 1 Phase CG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0F
Source 1 Phase AB or AC Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A11
Source 1 Phase BC or BA Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A13
Source 1 Phase CA or CB Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A15
Source 1 Phase AB or AC Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A17
Source 1 Phase AB or AC Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A18
Source 1 Phase BC or BA Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1A
Source 1 Phase BC or BA Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1B
Source 1 Phase CA or CB Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1D
Source 1 Phase CA or CB Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1E
Source 1 Auxiliary Voltage RMS
V
F060
0
Table B–9: MODBUS MEMORY MAP (Sheet 8 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...