1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 12. Wired remote controller
communication error (Indoor unit)
1 times
2 times
Continuous
12
E: 18. External communication error (Indoor
unit)
1 times
8 times
Continuous
18
E: 22. Indoor unit capacity error (Indoor
unit)
2 times
2 times
Continuous
22
E: 23. Combination error (Outdoor unit)
2 times
3 times
Continuous
23
E: 26. Address setting error in wired remote
controller (Indoor unit)
2 times
6 times
Continuous
26
E: 29. Connected unit number error (Indoor
unit)
2 times
9 times
Continuous
29
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times
2 times
Continuous
32
E: 33. Indoor unit motor electricity
consumption detection error (Indoor unit)
3 times
3 times
Continuous
33
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times
5 times
Continuous
35
E: 39. Indoor unit power supply error for fan
motor (Indoor unit)
3 times
9 times
Continuous
39
E: 3A. Indoor unit communication circuit
(wired remote controller) error
3 times
10 times
Continuous
3A
E: 41. Room temperature sensor error
(Indoor unit)
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times
2 times
Continuous
42
E: 45. Refrigerant leakage sensor error
(Indoor unit)
4 times
5 times
Continuous
45
E: 45. Refrigerant leakage sensor
deterioration (Indoor unit)
4 times
5 times
Continuous
45
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times
1 times
Continuous
51
E: 53. Drain pump error (Indoor unit)
5 times
3 times
Continuous
53
E: 57. Damper (Open/Close) detection limit
switch error
5 times
7 times
Continuous
57
E: 57. Damper (Open/Close) simultaneous
detection limit switch error (Indoor unit)
5 times
7 times
Continuous
57
E: 58. Intake grille error (Indoor unit)
5 times
8 times
Continuous
58
5 times
15 times
Continuous
5U
E: 62. Outdoor unit model information error
(Outdoor unit)
6 times
2 times
Continuous
62
E: 64. Active filter voltage error (Outdoor
unit)
6 times
4 times
Continuous
64
E: 65. IPM error (Outdoor unit)
6 times
5 times
Continuous
65
E: 71. Discharge thermistor error (Outdoor
unit)
7 times
1 times
Continuous
71
E: 72. Compressor thermistor error
(Outdoor unit)
7 times
2 times
Continuous
72
1-3. Error code table (Indoor unit and wired remote controller)
- (03-2) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...