2-22. E: 58. Intake grille error (Indoor unit)
Indicator
Indoor unit
Operation indicator
5 time flash
Timer indicator
8 time flash
Economy indicator
Continuous flash
Error code
E: 58
Detective actuator
Indoor unit main PCB
When the Micro switch is detected open while running
the compressor.
Micro switch
Forecast of cause
Micro switch failure
Shorted connector/wire
Main PCB failure
Check point 1. Check limit switch
•
Check operation of Micro switch. (any blocking by dust, etc.)
•
Remove Micro switch and check ON/OFF switching operation by using a meter.
-> If micro switch is detective, replace it.
↓
Check point 2. Check connector (CN11)/wire
Check loose contact of CN11/shorted wire (pinched wire).
-> Replace micro switch if the wire is abnormal
↓
Check point 3. Replace the main PCB
If Check Point 1 and 2 do not improve the symptom, replace the main PCB.
↓
End
2-22. E: 58. Intake grille error (Indoor unit)
- (03-38) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...