Dry operation
During dry operation, fan speed setting can not be changed as shown in “Fan speed” above.
Heating operation
Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be-
low.
On the other hand, if switched in HIGH—QUIET, the indoor motor will run at a constant airflow of
HEAT operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Heating: Auto)
When the room
temperature rises
When the room
temperature drops
LOW mode
MED mode
MED+ mode
Tr - Ts ≥ -1
°C
-2
°C > Tr - Ts
Tr - Ts ≥ -1.5
°C
-1.5
°C
> Tr - Ts ≥ -2.5
°C
-2.5
°C > Tr - Ts
-1
°C
> Tr - Ts ≥ -2
°C
Cool air prevention control (heating mode)
The maximum value of the indoor fan speed is set as shown below, based on the detected tempera-
ture by the indoor heat exchanger sensor on heating mode.
•
Normal operation
42°C
Indoor heat exchanger
temperature rises
HIGH
or setting fan mode*
Cool air prevention
S-LOW
Indoor heat exchanger
temperature drops
39°C
37°C
30°C
37°C
34°C
32°C
28°C
MED+
or setting fan mode*
LOW
or setting fan mode*
*: Lower speed is selected.
13 minutes later:
42°C
Indoor heat exchanger
temperature rises
HIGH
or setting fan mode*
Indoor heat exchanger
temperature drops
39°C
37°C
30°C
37°C
34°C
32°C
28°C
MED+
or setting fan mode*
LOW
or setting fan mode*
*: Lower speed is selected.
LOW
or setting fan mode*
LOW
or setting fan mode*
3-1. Indoor fan control
- (04-34) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...