![Fujitsu ABHG18KRTA Service Manual Download Page 455](http://html.mh-extra.com/html/fujitsu/abhg18krta/abhg18krta_service-manual_118013455.webp)
1-10. Simple remote controller (UTY-RSNGM)
DIP switch
SW1
Prohibited
SW2
Dual remote controller setting
SW3
°F/°C switch
SW4
Prohibited
SW5
Prohibited
SW6
Prohibited
¢
Switch location
1
2
3
4
5
6
DIP Switch
ON
OFF
¢
DIP switch setting
SW2: Dual remote controller setting
Set the remote controller SW2 according to the following table.
Number of remote controller
Primary unit
Secondary unit
Factory setting
SW2
SW2
1 (Normal)
OFF
—
♦
2 (Dual)
OFF
ON
1 2 3
1 2 3
1 2 3
Indoor unit
Remote controller cable
Primary unit
Secondary
unit
Remote controller
SW3: Switching temperature unit °F / °C
Displayed temperature unit can be switched between Fahrenheit (°F) and Celsius (°C).
SW3
Fahrenheit (°F) / Celsius (°C)
Factory setting
OFF
°C
♦
ON
°F
1-10. Simple remote controller (UTY-RSNGM)
- (05-51) -
1. Function settings (for indoor unit)
FIELD
WORKING
FIELD
WORKING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...