c. Select the correction method.
Correct the wiring manually.*2
Proceed to step 6.
Use the Automatic wiring correction function.*1
Proceed to step 5.
Write down the same results in the label on the reverse side of the service panel.
The results recorded are needed at the time of servicing.
<Result Table>
A
B
C
D
E
F
1
2
3
4
5
6
7
A
B
C
D
E
F
NOTES:
• *1: By using this function, the wiring is automatically corrected according to the piping.
• *2: When correcting the wiring manually, please disconnect the power supply or turn off the
breaker during results display, and then change the wiring manually according to the obtained
test results.
For example, in Example 1, the wirings connected to the terminals B and C is to be exchanged
manually.
5.
During results display, press the CHECK switch for 3 seconds or more.
After LEDs A to F have lit in turn, all LEDs will light up indicating that the automatic wiring cor-
rection is completed.
(2-blink)
MONITOR
POWER
ERROR
/MODE
(GRN) (RED)
A
B
C
D
E
F
6.
Disconnect the power supply or turn off the breaker and wait 10 minutes then turn the power
back on and perform test run.
NOTE:
If you do not disconnect the power supply or turn off the breaker, normal operation is not
possible.
Notices:
• If an error occurs during check run it will be suspended. Correct the error and start check run
again.
• After the check run, if automatic wiring correction is carried out, the indoor unit’s position will be
modified to match the piping. (Note that the display of the optional remote controller changes.)
• If you start check run again after the automatic wiring correction is finished, the modification will
be reset.
3-1. Check run
- (05-60) -
3. Check and test
FIELD
WORKING
FIELD
WORKING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...