Wall mounted type (For KGTB and KGTE)
•
Rotation number range of compressor
Unit: rps
Connected model name
Minimum rotation number
Maximum rotation number
AOHG30KBTA4
AOHG36KBTA5
10
130
•
Limit of maximum speed based on outdoor temperature
A zone
26°C
B zone
C zone
D zone
23°C
20°C
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASHG07KGTB
ASHG09KGTB
A zone
102
74
63
54
ASHG12KGTB
ASHG14KGTB
B zone
102
87
74
63
ASHG07KGTE
ASHG09KGTE
C zone
130
111
94
80
ASHG12KGTE
ASHG14KGTE
D zone
130
130
130
130
1-1. Cooling operation
- (04-5) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABHG18KRTA