![Fujitsu ABHG18KRTA Service Manual Download Page 13](http://html.mh-extra.com/html/fujitsu/abhg18krta/abhg18krta_service-manual_118013013.webp)
¢
Medium static pressure duct type
Model name
ARXG22KMLB
Power supply
1Ø 230 V ~50 Hz
Available voltage range
198—264 V
Capacity
kW class
6.0
Input power
W
94
Running current
A
0.60
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,100
MED
910
LOW
750
QUIET
580
Heating
HIGH
1,100
MED
910
LOW
750
QUIET
580
Type × Q'ty
Sirocco fan × 2
Motor output
W
106
Recommended static pressure
Pa
30 to 150
Sound pressure level *
Cooling
HIGH
dB (A)
31
MED
29
LOW
27
QUIET
25
Heating
HIGH
31
MED
29
LOW
27
QUIET
25
Sound power level
Cooling
dB (A)
60
Heating
62
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1,000 × 39.9
Fin pitch
mm
1.40
Rows × Stages
3 × 14
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
—
Dimensions
(H × W × D)
Net
mm
270 × 1,135 × 700
Gross
300 × 1,320 × 790
Weight
Net
kg
35
Gross
43
Connection
pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas
Ø12.70 (Ø1/2)
Method
Flare
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Drain hose
Material
Steel
Size
mm
Ø 35.7 (I.D.), Ø 38.1 (O.D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Standard static pressure: 35 Pa.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-7) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...