2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 12
Detective actuator
Indoor unit
Main PCB
When the indoor unit cannot receive the signal from
wired remote controller more than 1 minute during
normal operation.
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
•
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
↓
Check Point 1-2. Check the wired remote controller and main PCB
[Compact cassette, slim duct, floor, and ceiling types]
Check voltage at CN14 (terminal 1—3) of main PCB or communication PCB. (Power supply to the
remote controller)
•
If it is DC 12 V, the remote controller is failure. (Main PCB is normal)
–
Replace the remote control
•
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
–
Replace the main PCB
[Wall mount type for KGTB, KGTE, 18-24KMTB, KMTE, KMCE, KETA, KETE(-B)]
Check voltage at CN300 (terminal 1—2) of main PCB or communication PCB. (Power supply to the
remote controller)
•
If it is DC 12 V, the remote controller is failure. (Main PCB is normal)
–
Replace the remote control
•
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
–
Replace the main PCB
[Wall mount type for 07-14KMTB, KMCC]
Check voltage at CNC01 (terminal 1—3) of main PCB or communication PCB. (Power supply to the
remote controller)
•
If it is DC 13 V, the remote controller is failure. (Main PCB is normal)
–
Replace the remote control
•
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
–
Replace the main PCB
[Mini duct type]
Check voltage at CN300 (terminal 1—3, terminal 1—2) of main PCB. (3-wire remote controller, 2-
wire remote controller) (Power supply to the remote controller)
•
If it is DC 12 V, the remote controller is failure. (Main PCB is normal)
–
Replace the remote control
•
If it is DC 0 V, the main PCB is failure. (Check remote controller once again)
–
Replace the main PCB
2-3. E: 12. Wired remote controller communication error (Indoor unit)
- (03-18) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...