2-34. E: 86. High pressure switch error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
8 time flash
Timer indicator
6 time flash
Economy indicator
Continuous flash
Error code
E: 86
Detective actuator
Outdoor unit main PCB
When pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
Connector connection failure
Pressure sensor failure
Main PCB failure
Check point 1. Reset power supply and operate
Does abnormal LED indication show again?
↓
Check point 2. Check output voltage of main
PCB
Make sure circuit diagram of outdoor unit and
check terminal voltage at thermistor (DC 5.0 V
± 5%).
NOTE:
For details of thermistor connector, re-
fer to
TECHNICAL DATA AND PARTS LIST
on page 02-117.
If the voltage is not correct, replace main PCB.
↓
Check point 3. Check pressure switch
Check if connector is loose or cable is open.
-> If no abnormal connection is found, replace
pressure switch.
After replacing pressure switch, check operating
condition and pressure in operation.
↓
End
• Characteristics of pressure switch
Pressure switch 1
Contact: Short → Open
4.2 ±0.1 MPa
Contact: Open → Short
3.2 ±0.15 MPa
CN37
Pressure switch 2
Contact: Short → Open
37
+0
-0.2
MPa
Contact: Open → Short
2.9 ±0.2 MPa
CN36
2-34. E: 86. High pressure switch error (Outdoor unit)
- (03-50) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...