3-4. No cooling/No heating
Forecast of cause
Indoor unit error
Outdoor unit error
Effect by surrounding environment
Connection pipe/Connection wire failure
Refrigeration cycle failure
Check point 1. Check Indoor unit
•
Does Indoor unit fan run in the HIGH mode?
•
Is air filter dirty?
•
Is heat exchanger clogged?
•
Check if energy save function is operated.
↓
Check point 2. Check outdoor unit operation
•
Check if outdoor unit is operating.
•
Check any objects that obstruct the air flow route.
•
Check if heat exchanger is clogged.
•
Is the valve open?
↓
Check point 3. Check site condition
•
Is capacity of Indoor unit fitted to the room size?
•
Any windows open or direct sunlight?
↓
Check point 4. Check indoor/outdoor installation condition
•
Check connection pipe (specified pipe length and pipe diameter?)
•
Check any loose or removed communication line.
→ If there is an abnormal condition, correct it by referring to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
↓
Check point 5. Check Refrigeration cycle
•
Check if strainer is clogged (Refer to the figure below).
•
Measure gas pressure, and if there is a leakage, correct it.
•
Check if EEV open or there is a capillary tube defect.
Refer to outdoor unit Electrronic Expansion Valve (EEV) or Capillary tube in
•
Check compressor.
Refer to compressor in
Refer to inverter compressor in
NOTE:
When recharging the refrigerant, make sure to perform vacuuming,
and recharge the specified amount.
MPa
MPa
↓
End
3-4. No cooling/No heating
- (03-67) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...