![Fujitsu ABHG18KRTA Service Manual Download Page 24](http://html.mh-extra.com/html/fujitsu/abhg18krta/abhg18krta_service-manual_118013024.webp)
¢
Floor type
Model name
AGHG09KVCA
AGHG12KVCA
AGHG14KVCA
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Capacity
kW class
2.5
3.5
4.0
Input power
W
16
20
23
Running current
A
0.15
0.18
0.20
Fan
Airflow rate
Cooling
HIGH
m
3
/h
530
600
650
MED
440
490
520
LOW
360
380
400
QUIET
270
270
270
Heating
HIGH
530
600
650
MED
460
510
540
LOW
380
410
430
QUIET
270
270
270
Type × Q'ty
Cross flow fan × 2
Motor output
W
16 × 2
Sound pressure level *
Cooling
HIGH
dB (A)
39
42
44
MED
34
36
38
LOW
28
30
31
QUIET
22
22
22
Heating
HIGH
39
42
44
MED
35
38
39
LOW
30
32
33
QUIET
22
22
22
Sound power level
Cooling
dB (A)
52
55
56
Heating
52
55
56
Heat exchanger type
Dimensions (H × W × D)
mm
378 × 550 × 26.6
Fin pitch
1.2
Rows × Stages
2 × 18
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Polystyrene
Color
White
Dimensions
(H × W × D)
Net
mm
600 × 740 × 200
Gross
700 × 820 × 310
Weight
Net
kg
14
Gross
18
Connection pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas
Ø9.52 (Ø3/8)
Method
Flare
Drain hose
Material
PP + LLDPE
Tip diameter
mm
Ø13.8 (I.D.), Ø15.8 to Ø16.7 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
30 or less
Remote controller type
Wireless (Wired, Simple mobile app [option])
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
–
Measured values in manufacturer’s anechoic chamber.
–
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-1. Indoor unit
- (01-18) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...