![Fujitsu ABHG18KRTA Service Manual Download Page 465](http://html.mh-extra.com/html/fujitsu/abhg18krta/abhg18krta_service-manual_118013465.webp)
¢
Failure indication of check-run judgment
The check run stops when there is an error, and the LED shows the relevant error indication. When
you encounter the errors described here, perform checking by using the cooling test run of the indoor
unit.
•
Temperature out of range judgment
(2-blink)
blink
(High speed)
MONITOR
POWER
ERROR
/MODE
(GRN) (RED)
A
B
C
D
E
F
•
Wiring/piping number difference
MONITOR
POWER
ERROR
/MODE
(GRN) (RED)
A
B
C
D
E
F
blink
(High speed)
blink
(High speed)
OR
(2-blink)
(2-blink)
¢
Redisplaying the results of check run
• When checking the content of automatic wiring correction, push the CHECK switch. The results of
the check run is displayed. You can compare the result that is recorded in step (4) of "Chapter
3-1-3.
"Operating procedure for check run"
• If the automatic wiring correction is not completed, the POWER/MODE LED blinks twice and the
MONITOR LED turns off.
¢
Memory resetting of automatic wiring correction
CAUTION
When relocating the unit, reset the memory beforehand, or the unit may not function normally.
1. Push the CHECK switch.
The LED lights as shown in “
"Redisplaying the results of check run"
2. When the LED is on, press the CHECK switch for more than 3 seconds.
3. The LEDs from A to F light in sequence, and then all LEDs light to indicate the completion of
the memory resetting of automatic wiring correction.
4. Disconnect the power supply or turn off the breaker.
3-1. Check run
- (05-61) -
3. Check and test
FIELD
WORKING
FIELD
WORKING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...