Check point 4. Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
RED
WHITE
BLACK
+
-
3
2
1
•
Check if indicated value swings between AC 90 V and AC 270 V at the outdoor unit terminal 1
—3.
•
If it is abnormal, check the parts below.
–
Outdoor unit fan motor in
–
•
If outdoor fan motor is abnormal, replace outdoor unit fan motor and main PCB.
•
If active filter module is abnormal, replace it.
•
If the checked parts are normal, replace the main PCB.
↓
End
Check point 1-2. Check external cause such as noise
•
Check the complete insulation of the grounding.
•
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
↓
End
2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- (03-15) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING