4.
After the check run is completed, results will be displayed. Fill the displayed results in the result
table accordingly.
•
If the connection is correct (Example: When 4 indoor units are connected)
After the number of connected units are displayed, the LED for each unit will light up in order
from A to D.
MONITOR
POWER
ERROR
/MODE
(GRN) (RED)
A
B
C
D
E
F
(2-blink)
(7 s)
(7 s)
(7 s)
(7 s)
•
If the connection is incorrect (Example: When connection of B and C of the 4 units are
reversed)
After the number of connected units are displayed, B and C will light up in reverse.
MONITOR
POWER
ERROR
/MODE
(GRN) (RED)
A
B
C
D
E
F
(7 s)
(7 s)
(7 s)
(7 s)
(2-blink)
NOTES:
• Automatic wiring correction will not be completed if the power supply is disconnected while dis-
playing the results. To confirm the automatic wiring correction, be sure to carry out step 5.
• If frost is formed on the outdoor unit while displaying the results, automatic defrost function will
be operated. Proceed to step 5 after the defrost function is finished.
3-1. Check run
- (05-58) -
3. Check and test
FIELD
WORKING
FIELD
WORKING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...