8-3. Current release control
The rotation number of compressor is controlled so that the outdoor unit input current does not ex-
ceeds current limit value set according to the outdoor temperature.
The rotation number of compressor returns according to the operation mode, when the current be-
comes lower than the release value.
¢
Model: AOHG30KBTA4
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
8.0 A
7.5 A
46°C ≤ Ta < 50°C
9.5 A
9.0 A
40°C ≤ Ta < 46°C
11.0 A
10.5 A
12°C ≤ Ta < 40°C
14.0 A
13.5 A
2°C ≤ Ta < 12°C
14.0 A
13.5 A
Ta < 2°C
14.0 A
13.5 A
Heating
17°C ≤ Ta
10.5 A
10.0 A
12°C ≤ Ta < 17°C
13.0 A
12.5 A
5°C ≤ Ta < 12°C
15.0 A
14.5 A
Ta < 5°C
15.0 A
14.5 A
¢
Model: AOHG36KBTA5
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
8.0 A
7.5 A
46°C ≤ Ta < 50°C
9.5 A
9.0 A
40°C ≤ Ta < 46°C
11.0 A
10.5 A
12°C ≤ Ta < 40°C
14.0 A
13.5 A
2°C ≤ Ta < 12°C
14.0 A
13.5 A
Ta < 2°C
14.0 A
13.5 A
Heating
17°C ≤ Ta
10.5 A
10.0 A
12°C ≤ Ta < 17°C
13.0 A
12.5 A
5°C ≤ Ta < 12°C
15.0 A
14.5 A
Ta < 5°C
16.5 A
16.0 A
8-3. Current release control
- (04-79) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...