5. Service parts information
5-1. Compressor
Diagnosis method of compressor (If outdoor unit LED displays error, refer to troubleshooting)
Does not start up
Stops soon after starting up
Abnormal noise
↓
↓
↓
Is there open or loose con-
nection cable?
Is there open or loose con-
nection cable?
Check if vibration noise by
loose bolt or contact noise of
piping is happening.
↓
↓
↓
Check main PCB, connection
of compressor, and winding
resistance.
(Refer to the next page)
→ If there is no failure, the
defect of compressor is con-
sidered (Locked compressor
due to clogged dirt or less oil)
Is gas pipe valve open?
(Low pressure is too low)
Defective compressor can be
considered.
(due to inside dirt clogging or
broken component)
↓
↓
↓
Replace compressor.
Check if refrigerant is
leaking.
MPa
MPa
Replace compressor.
↓
↓
↓
End
Check if strainer is clogged.
(Refer to outdoor EEV or
capillary tube in this chap-
ter.)
End
↓
Check main PCB, connection of compressor and winding resis-
tance. (Refer to the next page)
→ If there is no failure, the defect of compressor can be consid-
ered. (Compression part broken or valve defective.)
↓
Replace compressor.
↓
End
5-1. Compressor
- (03-83) -
5. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...