2-21. E: 57. Damper (Open/Close) simultaneous detection limit
switch error (Indoor unit)
Indicator
Indoor unit
Operation indicator
5 time flash
Timer indicator
7 time flash
Economy indicator
Continuous flash
Error code
E: 57
Detective actuator
Indoor unit main PCB
When the limit switch detects open and close at the
simultaneous.
Limit switch
Forecast of cause
Limit switch failure
Shorted connector/wire
Controller PCB failure
Check point 1. Check limit switch
•
Check operation of limit switch. (any blocking by dust, etc.)
•
Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
↓
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
↓
Check point 3. Replace the main PCB
If Check Point 1, 2 do not improve the symptom, replace the main PCB.
↓
End
2-21. E: 57. Damper (Open/Close) simultaneous detection limit switch error (Indoor
unit)
- (03-37) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...