![Fujitsu ABHG18KRTA Service Manual Download Page 245](http://html.mh-extra.com/html/fujitsu/abhg18krta/abhg18krta_service-manual_118013245.webp)
2-13. E: 3A. Indoor unit communication circuit (wired remote
controller) error
Indicator
Indoor unit
Operation indicator
3 time flash
Timer indicator
10 time flash
Economy indicator
Continuous flash
Error code
E: 3A
Detective actuator
Wired remote controller (2-wire)
Detect the communication error of microcomputer and
communication PCB.
Indoor unit controller PCB circuit
Forecast of cause
Communication PCB defective
Indoor unit main PCB defective
Check point 1. Check the connection of terminal
•
After turning off the power supply, check and correct the followings
Indoor unit - Check the connection the communication PCB and the main PCB
↓
Check Point 2 : Replace the communication PCB
If the Check point 1 is ok, replace the communication PCB
↓
Check Point 3 : Replace the main PCB
If condition is doesn’t change, replace the main PCB
↓
End
2-13. E: 3A. Indoor unit communication circuit (wired remote controller) error
- (03-29) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 08 08 SR_CH01_MU004EG_06 ...
Page 59: ...2 TECHNICAL DATA AND PARTS LIST 2022 08 08 SR_CH02_MU004EG_11 ...
Page 62: ......
Page 213: ...3 TROUBLESHOOTING 2022 08 08 SR_CH03_MU004EG_07 ...
Page 216: ......
Page 316: ...6 2 Outdoor unit 03 100 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 317: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU004EG_08 ...
Page 320: ......
Page 403: ...5 FILED WORKING 2022 08 08 SR_CH05_MU004EG_08 ...