C - 19
Appendix C
•
Remote Control and Monitoring of Vission 20/20 Panel
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Notes:
1. The default password is VVNC and the default Port Number is 5900.
2. The SSVNC client is required only if the web browser option is enabled.
3. If the web browser option is not enabled then any normal VNC client without SSL/SSH support can be used;
SSVNC client will not work.
PLC REMOTE COMPRESSOR CONTROL OF VISSION 20/20
PLC remote compressor control of the Vission 20/20 panel (either via communications or hardwired) is accomplished
by placing the panel into Remote mode.
Remote Control Mode in the panel refers to two distinct ways of controlling the compressor.
1. Control via communication port. This can be accomplished through:
• Ethernet ( via Ethernet I/P or Modbus TCP/IP )
• Serial (RS485 Modbus RTU )
2. Control via Direct I/O (Digital inputs)
2. Enter the IP address and VNC Port Number as displayed in the image, Uncheck the “Verify All Certs” checkbox and
click on “Connect” button.
3. Type the VNC Password and you’re logged in.