3 – 6
Section 3
•
Hardware Architecture
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Condenser / Remote Oil Cooler Step #1 Output:
• This output is enabled when condenser control or
Remote Oil Cooler option is selected. A condenser /
Remote Oil Cooler fan or pump will be turned on or
off by this output.
Condenser / Remote Oil Cooler Step #2 Output:
• This output is enabled when condenser control or
Remote Oil Cooler option is selected. A condenser /
Remote Oil Cooler fan or pump will be turned on or
off by this output.
Condenser / Remote Oil Cooler Step #3 Output:
• This output is enabled when condenser or Remote
Oil Cooler control option is selected. A condenser /
Remote Oil Cooler fan or pump will be turned on or
off by this output.
Condenser / Remote Oil Cooler Step #4 Output:
• This output is enabled when condenser or Remote
Oil Cooler control option is selected. A condenser /
Remote Oil Cooler fan or pump will be turned on or
off by this output.
Auxiliary Inputs #1 - #8:
•
Optional inputs that can be configured as an alarm
or trip. Typically connected to external switched
devices.
Auxiliary Outputs #1 - #4:
•
Optional inputs that can be configured as an alarm
or trip. Typically connected to external switched
devices.
Analog Inputs
Refer to Table 3-2.
Motor Current:
• Default is a 0-5 Amp current transformer (CT). Current
transformer ratio is set in the calibration screen.
Suction Pressure:
• Default signal is 4-20mA. Suction pressure trans-
ducer range and calibration is set in the calibration
screen.
Discharge Pressure
• Default signal is 4-20mA. Discharge pressure trans-
ducer range and calibration are set in the calibration
screen.
Oil Filter Inlet Pressure:
•
Default signal is 4-20mA. Oil filter pressure trans
-
ducer range and calibration are set in the calibration
screen.
Oil Manifold Pressure:
• Default signal is 4-20mA. Oil manifold pressure trans-
ducer range and calibration are set in the calibration
screen.
Economizer Pressure:
• Default signal is 4-20mA. Economizer pressure trans-
ducer range and calibration are set in the calibration
screen.
Slide Valve Position:
• Reads the 0-5 volt signal back from the slide posi-
tion motor actuator to indicate current slide valve
position.
Volume Position:
• Reads the 0-5 volt signal back from the slide volume
motor actuator to indicate current volume position.
Suction Temperature:
• Default signal is RTD. Suction temperature calibra-
tion is set in the calibration screen.
Discharge Temperature:
• Default signal is RTD. Discharge temperature calibra-
tion is set in the calibration screen.
Oil Separator Temperature:
• Default signal is RTD. Oil separator temperature cali-
bration is set in the calibration screen.
Oil Manifold Temperature:
• Default signal is RTD. Oil manifold temperature cali-
bration is set in the calibration screen.
Process Temperature:
• Default signal is 4-20mA. Process temperature cali-
bration and range are set in the calibration screen.
Chiller Inlet Temperature:
• Default signal is 4-20mA. Measures separator level.
Chiller Inlet Temperature calibration and range are
set in the calibration screen.
Condenser Pressure:
• Default signal is 4-20mA. Condenser pressure trans-
ducer range and calibration are set in the calibration
screen.
Remote Caphold:
• Default signal is 4-20mA. Active in “Direct I/O” mode.
Adjusts the capacity of the compressor from 0-100%,
proportional to the 4-20mA signal.
Auxiliary #1 - #16:
•
Flexible analog inputs that can be configured to con
-
trol, alarm or trip.
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......