D - 13
Appendix D
•
Vission 20/20 Communication Table
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Vilter
TM
Address
Ethernet
IP
Address
Modbus
Address
Command Name
Data
Type
Value
Mode
Lower
Range
Higher
Range
213
N62:16
40656
Slide Valve Setpoint #2
State Below Setpoint
INT
0 = N.O., 1 = N.C.
Read
214
N62:17
40657
No Oil Pump Pressure
Ratio
F-INT
Read
215
N62:18
40658
No Oil Pump Load Limit
%
F-INT
Read
Compressor VFD
216
N70:0
40670
VFD Gain (P)
F-INT
Read
217
N70:1
40671
VFD Reset (I)
F-INT
Read
218
N70:2
40672
VFD Rate (D)
F-INT
Read
219
N70:3
40673
Step 1 VFD Minimum
Slide Position
INT
Read
220
N70:4
40674
Step 1 VFD Maximum
Slide Position
INT
Read
221
N70:5
40675
Step 1 VFD Minimum
Speed (rpm)
INT
Read
222
N70:6
40676
Step 1 VFD Maximum
Speed (rpm)
INT
Read
223
N70:7
40677
2 Step VFD Control
Enabled
INT
0 = Disabled, 1 = Enabled
Read
224
N70:8
40678
Step 2 VFD Minimum
Slide Position
INT
Read
225
N70:9
40679
Step 2 VFD Maximum
Slide Position
INT
Read
226
N70:10
40680
Step 2 VFD Minimum
Speed (rpm)
INT
Read
227
N70:11
40681
Step 2 VFD Maximum
Speed (rpm)
INT
Read
228
N70:12
40682
Rapid Cycling VFD
Minimum Speed (rpm)
INT
Read
229
N70:13
40683
Rapid Cycling VFD
Maximum Speed (rpm)
INT
Read
230
N70:14
40684
Warm up Timer
F-INT
Read
231
N70:15
40685
Oil Restriction Setpoint
(rpm)
INT
Read
232
N70:16
40686
Oil Restriction Offset
(rpm)
INT
Read
233
N70:17
40687
Oil Restriction Solenoid
State Below Setpoint
INT
0 = "N.O.", 1 = "N.C."
Read
Cool Compression
234
N71:0
40700
Auto Load Enabled
INT
0 = Disabled, 1 = Enabled
Read
235
N71:1
40701
Auto Load @ Start
INT
Read
236
N71:2
40702
Auto Load Timer (mins)
F-INT
Read
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......