3 – 1
Section 3
•
Hardware Architecture
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Overview
The Vission 20/20 control panel utilizes X-86 PC technol-
ogy with a Linux operating system. For hardware archi-
tecture, see Figure 3-1.
The Vission 20/20 has the following attributes:
• Low power, Industrial rated X-86 CPU.
• 15” XGA, high resolution LCD display. (Outdoor view-
able LCD optional).
• 8-wire touch screen operator interface.
• Flexible and expandable I/O.
• NEMA-4 enclosure (NEMA-4X optional).
• Industrial temperature range design.
Figure 3-1. Hardware Architecture Overview
Digital Input/Output (I/O)
Refer to Table 3-1.
Compressor Start Output:
• When the Vission 20/20 signals the compressor to
start, this output is energized. When the Vission
20/20 signals the compressor to stop, this output is
de-energized.
Oil Pump Start Output:
• When the Vission 20/20 signals the oil pump to start,
this output is energized. When the Vission 20/20 sig-
nals the oil pump to stop, this output is de-energized.
Capacity Increase Output:
• This output is only active when the compressor is
running. When the Vission 20/20 determines that
the compressor should increase capacity by moving
the slide valve to a higher percentage, this output is
energized. Once the slide valve reaches 100%, this
output will not energize.
Capacity Decrease Output:
• This output is only active when the compressor is
running. When the Vission 20/20 determines that
the compressor should decrease capacity by moving
the slide valve to a lower percentage, this output is
energized. Once the slide valve reaches 0%, this out-
put will not energize.
Volume Increase Output:
• This output is only active when the compressor is
running. When the Vission 20/20 determines that
the compressor should increase Volume Index (VI) by
moving the volume slide to a higher percentage, this
output is energized. Once the volume slide reaches
100%, this output will not energize.
Volume Decrease Output:
• This output is only active when the compressor is run-
ning. When the Vission 20/20 determines that the
compressor should decrease Volume Index (VI) by
moving the volume slide to a lower percentage, this
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......