Section 7 • Alarms and Trips
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Low Oil Filter Inlet Pressure (Oil Filter Inlet Pressure)
This Safety will be active only when Cool Compression is not enabled. This is not a user adjustable setpoint. The
value is used to test for a failure in the measuring instrument.
Low Oil Filter In Pressure
Warning
Low Oil Filter In Pressure
Trip
Oil Filter Inlet Pressure <
-66.5 psig
Oil Filter Inlet Pressure <
Low Oil Filter In Pressure
Trip [-66.5 psig]
Low Oil Filter Outlet Pressure (Oil Filter Outlet Pressure)
This Safety will be active only when Cool Compression is not enabled. This is not a user adjustable setpoint. The
value is used to test for a failure in the measuring instrument.
Low Oil Filter Out Pressure
Warning
Low Oil Filter Out Pressure
Trip
Oil Manifold Pressure <
-66.5 psig
Oil Filter Inlet Pressure <
Low Oil Filter Out Pressure
Trip [-66.5 psig]
High Oil Injection Temp (Oil Injection Temperature)
This Safety will be active only when Cool Compression is not enabled. See Figure 7-5.
High Oil Injection Temp
Warning
High Oil Injection Temp
Inhibit
High Oil Injection Temp
Alarm
High Oil Injection Temp
Trip
Oil Injection Temperature
> High Oil Injection
Temperature Alarm
Oil Injection Temperature
> High Oil Injection
Temperature Alarm
Oil Injection Temperature
> High Oil Injection
Temperature Alarm
Oil Injection Temperature
> High Oil Injection
Temperature Trip
Low Oil Injection Temp (Oil Injection Temperature)
The Alarm and Trip Setpoints are bypassed at start for a time period (setting of the Oil Injection Temperature
Safety Changeover timer). This Setpoint will be activated after the time delay has expired. The Warning condi-
tion goes off when the temperature goes below -100 or -73°C.
See Figure 7-5.
Low Oil Injection Temp
Warning
Low Oil Injection Temp
Alarm
Low Oil Injection Temp Trip
Oil Injection Temperature
< -100°F
Oil Injection Temperature
< Low Oil Injection
Temperature Alarm
Oil Injection Temperature
< Low Oil Injection
Temperature Trip
Oil Level #1 or #2 (Oil Level)
These safeties are available for Cool Compression Feature. This message will appear when Oil Level Float Switch
#1 or #2 input is de-energized.
Oil Level #1 or #2 Inhibit
Oil Level #1 or #2 Trip
Oil Level Float Switch #1
or #2 De-energized when
compressor is starting
Oil Level Float Switch #1 or
#2 De-energized
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......