Section 6
•
Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 6-15. Compressor Control Screen - Stop Load, Force Unload and Slide Valve Control
Capacity Slide Triggered Outputs
The Vission 20/20 offers two digital outputs that can be
triggered at a specified capacity slide position. By de
-
fault, the outputs are preselected for the economizer
and the hot gas bypass. However, these preselected out-
puts are customizable by the operator, see Figure 6-15.
Slide Valve Setpoint:
• Operator editable labels for the each output. Only
the Economizer Port 2 label is non-editable.
Slide %:
• Indicates the capacity slide position where the digital
output is triggered.
State Below Setpoint:
•
Defines the state of the digital output when the slide
position is below the “Slide %” setpoint. The operator
can choose between “N.O.” or “N.C.”. This setpoint
is not available for the Economizer Port 2, so the
Economizer Port 2 follows the setpoint of Economizer
Port 1.
Active:
• Check box to enable the digital output. There is no
check box to enable the Economizer Port 2 digital
output. The economizer Port 2 digital output is en-
abled when the compressor type selected from the
configuration screen is “VSM7” and the Economizer
Port 1 digital output is enabled.
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......