Section 10
•
Compressor Sequencing
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 10-11. Compressor Sequencing Screen - Sync Sequencing Parameters (Page 5)
Sync Sequencing Parameters
This screen offers the ability to sync Vission device’s in-
formation with Vission 20/20 slave compressors. This
feature is basically used in situations where the Vission
20/20 Compressor role needs to change from a Slave to
Master. Hence operator does not require to Add Vission
Devices again as Slave Compressors in the Sequencing
Network. For the Sync Sequencing Parameters screen
see Figure 10-11.
Sync:
• By pressing this button, the Vission device’s informa-
tion is sent over the network to the Vission 20/20
Slave Compressors.
NOTE
Follow these steps to use this feature:
1. Sync Data by pressing the Sync Button in the
Master compressor.
2. Change the intended Vission 20/20 Slave
Compressor to Master Compressor from the
Configuration Screen.
3. Log on to the Compressor Sequencing Screen
to view the Vission devices in the Devices List
Screen of the new Master Compressor.
Please make sure at the same time that there is only
one Master in the Compressor Sequencing Network
to ensure the proper working of the Compressor
Sequencing Algorithm.
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......