B - 39
Appendix B
•
Vission 20/20 Application Procedures
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
VPLUS (DC Motor) Setup Procedure for 20/20
Panel
INTRODUCTION
This document provides guidelines to setup a DC Motor
VPLUS oil cooling system control on the Vission 20/20
panel.
SCOPE
The Vilter
TM
standard VPLUS oil cooling system uses a
mini-temperature controller to monitor both discharge
and oil injection temperature, averages those tempera-
tures and compares the average to a setpoint. Based on
the error from the setpoint, the temperature control-
ler then sends a varying 4-20ma signal to a Dart speed
control board – which varies the speed of a DC motor.
The speed of the motor controls the amount of liquid re-
frigerant that is injected into the compressor to provide
oil cooling.
The Vission 20/20 has oil cooling controller algorithms
built into the program, and therefore allows for removal
of the temperature controller from the VPLUS panel.
This document provides instructions to help setup the
Vission 20/20 for VPLUS control.