7 – 10
Section 7 • Alarms and Trips
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
Add Oil to the Middle Sight Glass
Only when Cool Compression is enabled.
Add Oil to the Middle Sight
Glass
Oil Level < Open Low Oil
Level Switch
Analog AUX In 1-16
This message will appear when the Analog Aux in 1-16 exceeds / falls below the safety setting of the High / Low
Alarm Setpoint.
Analog Aux in 1-16
Warning
Analog Aux in 1-16 Inhibit
Analog Aux in 1-16 Alarm
Analog Aux in 1-16 Trip
Analog AUX In 1-16 > or <
Analog AUX In 1-16 Safety
Setting
Analog AUX In 1-16 > or <
Analog AUX In 1-16 Safety
Setting
Analog AUX In 1-16 > or <
Analog AUX In 1-16 Safety
Setting
Analog AUX In 1-16 > or <
Analog AUX In 1-16 Safety
Setting
Capacity Position Trip
This message will appear if the condition exists following any shutdown.
Capacity Position Trip
Capacity Slides failing
to unload < 5% during
Capacity Unload Cycle
Compressor Interlock Trip
Compressor Interlock Trip message will appear if the Motor Auxiliary contact fails to close before the
Compressor Starter Auxiliary Contact Bypass timer times out. Refer to the wiring diagram provided with unit.
Compressor Interlock
Inhibit
Compressor Interlock Trip
Motor Auxiliary Contact
Fails to Close when
Compressor is starting
Motor Auxiliary Contact
Fails to Close before
Compressor Starter
Auxiliary Contact Bypass
Timer times out
Digital AUX In 1-8
This message will appear when the Digital Aux in 1-8 is Active High / Low.
Digital Aux in 1-8 Warning
Digital Aux in 1-8 Inhibit
Digital Aux in 1-8 Alarm
Digital Aux in 1-8 Trip
Digital AUX In 1-8 > or <
Digital AUX In 1-8 Active
High / Low
Digital AUX In 1-8 > or <
Digital AUX In 1-8 Active
High / Low
Digital AUX In 1-8 > or <
Digital AUX In 1-8 Active
High / Low
Digital AUX In 1-8 > or <
Digital AUX In 1-8 Active
High / Low
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......