26 – 3
Section 26
•
Remote Oil Cooler
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
be set high enough to prevent hunting but not too
high or it will cause control system overshoot.
D = Derivative (rate):
• Used to adjust the capacity control action, account-
ing for how fast the error is changing, positively or
negatively.
Maximum Speed:
•
This setpoint defines the percentage maximum speed
for the Remote Oil Cooler VFD Fan to run for the con-
tinuous step delay time to increase the Remote Oil
Cooler steps. E.g. let’s say setpoint is kept at 95%.
Then the Remote Oil Cooler VFD fan will have to run
at a speed of 95% or more to advance to the next
step. The Maximum Speed can be set as 100%, which
is when the analog output (at which the Remote Oil
Cooler VFD fan is connected) reaches 20mA in its
normal range of 4-20mA.
Minimum Speed:
•
This setpoint defines the percentage minimum speed
for the Remote Oil Cooler VFD Fan to run for the con-
tinuous step delay time to decrease the Remote Oil
Cooler steps. E.g. let’s say setpoint is kept at 5%. Then
the Remote Oil Cooler VFD fan will have to run at a
speed of 5% or less to advance to the next step. The
Minimum Speed can be set as 0%, which is when the
analog output (at which Remote Oil Cooler VFD fan is
connected) reaches 4mA in its normal range of 4-20
mA.
Figure 26-2. Remote Oil Cooler VFD Screen (Page 2)
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......