14 – 8
Section 14
•
Slide Calibration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Problem
Reason
Solution
The actuator goes into calibration mode
spontaneously.
The white calibrate wire in the
grey Turck cable is grounding
intermittently.
Tape the end of the white wire in
the panel and make sure that it
cannot touch metal.
A very strong source of elec-
tromagnetic interference (EMI),
such as a contactor, is in the
vicinity of the actuator or grey
cable.
Increase the distance between
the EMI source and the actuator.
Install additional metal shielding
material between the EMI source
and the actuator or cable.
There is an intermittent failure of
the position sensor
Replace the actuator.
The actuator goes into calibration mode
every time power is restored after a power
loss
The motor brake is not working
properly.
Get the motor brake to where it
operates freely and recalibrate.
The position sensor’s EEPROM
memory has failed
Replace the actuator.
The actuator does not transmit the correct
position after a power loss.
The motor was manually moved
while the position sensor was
not powered.
Recalibrate.
The motor brake is not working
properly.
Get the motor brake to where it
operates freely and recalibrate.
The position sensor’s EEPROM
memory has failed
Replace the actuator.
There is a rapid clicking noise when the mo-
tor is operating.
The photo-chopper is mis-
aligned with the slotted
optocouplers.
Try to realign or replace the
actuator.
The photo-chopper is positioned
too low on the motor shaft.
Adjust the photo-chopper so that
the fence extends further into the
optocoupler slots.
A motor bearing has failed
Replace the actuator.
The motor operates in one direction only
There is a loose connection in
the screw terminal blocks.
Tighten
There is a loose or dirty connec-
tion in the yellow Turck cable.
Clean an tighten
The position sensor has failed.
Replace the actuator.
There is a broken motor lead or
winding
Replace the actuator.
Table 14-2. Slide Valve Troubleshooting Guide (2 of 3)
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......